Transient Stability Analysis of Grid-Forming Converters with Current Limiting Considering Asymmetrical Grid Faults

Systems and Control 2025-11-20 v1 Systems and Control

Abstract

Under asymmetrical faults, analyzing the transient stability of grid-forming voltage-source converters (GFM-VSCs) becomes essential because their behavior fundamentally differs from that under symmetrical faults. When current limiting is activated under asymmetrical faults, the point-of-common-coupling voltage of a GFM-VSC contains both positive- and negative-sequence components, and the interaction between these components generates a non-negligible negative-sequence-driven active power. However, the transient stability of GFM-VSCs under asymmetrical faults has not been sufficiently investigated, and the influence of negative-sequence-driven active power remains unclear. Accordingly, this letter derives the P-{\delta} curve of a GFM-VSC with an elliptical current limiter under asymmetrical faults by explicitly accounting for negative-sequence effects. This enables a more accurate transient stability assessment when extending conventional symmetrical-fault analyses to asymmetrical conditions. The theoretical analysis is validated by the agreement between the derived P-{\delta} curve and both simulation and experimental results.