English

A Fault Location Method Based on Electromagnetic Transient Convolution Considering Frequency-Dependent Parameters and Lossy Ground

Signal Processing 2024-01-02 v2 Computational Engineering, Finance, and Science

Abstract

As the capacity of power systems grows, the need for quick and precise short-circuit fault location becomes increasingly vital for ensuring the safe and continuous supply of power. In this paper, we propose a fault location method that utilizes electromagnetic transient convolution (EMTC). We assess the performance of a naive EMTC implementation in multi-phase power lines by using frequency-dependent parameters in real fault simulation, while using constant parameters in pre-calculation. Our results show that the location error increases as the distance between the fault location and the measurement location increases. Therefore, we adopt the aerial mode transients after phase-mode transformation to perform the convolution, which reduces the influence of frequency-dependence and ground loss. We conduct numerical experiments in a 3-phase 100-km transmission line, a radial distribution network and IEEE 9-bus system under different fault conditions. Our results show that the proposed method achieves tolerable location errors and operates efficiently through direct convolution of the real fault-generated transient signals and the pre-stored calculated transient signals.

Keywords

Cite

@article{arxiv.2212.14354,
  title  = {A Fault Location Method Based on Electromagnetic Transient Convolution Considering Frequency-Dependent Parameters and Lossy Ground},
  author = {Guanbo Wang and Chijie Zhuang and Jun Deng and Zhicheng Xie},
  journal= {arXiv preprint arXiv:2212.14354},
  year   = {2024}
}
R2 v1 2026-06-28T07:56:07.664Z