Complex-Vector Power and Cross-Phase Unbalance in Three-Phase Systems
Abstract
Unbalanced three-phase systems still lack a compact phasor-domain representation of power that makes phase asymmetry explicit while remaining consistent with established apparent-power definitions. This paper addresses that point through a complex-vector power formulation for sinusoidal steady-state operation. The proposed representation supplements the classical dot-product expression of complex power with the cross product of voltage and current phasors, thereby retaining the usual active and reactive terms while making explicit a cross-phase unbalance vector that captures antisymmetric interphase relations. In this way, apparent power is separated into intraphase and cross-phase contributions, and its norm is preserved under the power-invariant Fortescue transformation. The formulation is extended to three-phase four-wire systems by introducing equivalent coordinates that preserve the effective apparent-power norm for the chosen voltage reference. Only standard complex numbers and matrices are required. Numerical examples show operating conditions in which a non-negligible part of the apparent-power structure is associated with cross-phase unbalance and cannot be inferred from active and reactive power alone. The proposed formulation thus provides a compact phasor-based descriptor of unbalance that complements established apparent-power theories by making explicit a component that is not accessible from scalar apparent-power representations.
Keywords
Cite
@article{arxiv.2604.25473,
title = {Complex-Vector Power and Cross-Phase Unbalance in Three-Phase Systems},
author = {Juan Carlos Bravo-Rodríguez and Juan Carlos del-Pino-López and Francisco Casado-Machado},
journal= {arXiv preprint arXiv:2604.25473},
year = {2026}
}
Comments
8 pages, 1 figure, submitted to IEEE Trans. on Power Delivery