English

Recovery of Power Flow to Critical Infrastructures using Mode-dependent Droop-based Inverters

Systems and Control 2021-02-02 v1 Systems and Control

Abstract

Recovery of power flow to critical infrastructures, after grid failure, is a crucial need arising in scenarios that are increasingly becoming more frequent. This article proposes a power transition and recovery strategy by proposing a mode-dependent droop control-based inverters. The control strategy of inverters achieves the following objectives 1) regulate the output active and reactive power by the droop-based inverters to a desired value while operating in on-grid mode 2) seamless transition and recovery of power flow injections into the critical loads in the network by inverters operating in off-grid mode after the main grid fails; 3) require minimal information of grid/network status and conditions for the mode transition of droop control. A framework for assessing the stability of the system and to guide the choice of parameters for controllers is developed using control-oriented modeling. A comprehensive controller hardware-in-the-loop-based real-time simulation study on a test-system based on the realistic electrical network of M-Health Fairview, University of Minnesota Medical Center, corroborates the efficacy of the proposed controller strategy.

Keywords

Cite

@article{arxiv.2102.00046,
  title  = {Recovery of Power Flow to Critical Infrastructures using Mode-dependent Droop-based Inverters},
  author = {Soham Chakraborty and Sourav Patel and Murti V Salapaka},
  journal= {arXiv preprint arXiv:2102.00046},
  year   = {2021}
}